Blogue

Transformer Winding Resistance Test: What the Results Tell Engineers

A transformer winding resistance test can reveal problems that are difficult to identify from a visual inspection alone. An unusual reading may point to a loose connection, a damaged conductor, or a tap-changer contact that needs further investigation.

However, a resistance value is only useful when it is compared under the right conditions. Temperature, tap position, winding connection, test equipment, and the factory baseline can all affect the interpretation.

For transformer buyers, EPC contractors, and maintenance engineers, the key question is:

Does the test report provide enough information to distinguish a genuine problem from a difference in test conditions?

This guide explains what winding resistance results mean, how temperature correction works, and what to request before a transformer leaves the factory.

What Is a Transformer Winding Resistance Test?

A transformer winding resistance test measures the DC resistance of a winding and the electrical connections included in the measurement path.

A test instrument applies a controlled direct current and measures the voltage drop. The resistance is calculated as:

Resistance (Ω) = Voltage (V) ÷ Current (A)

Depending on the transformer design and test plan, measurements are taken between specified winding terminals and at relevant tap positions.

The test is commonly performed during:

  • Factory routine testing and factory acceptance testing, or FAT
  • Site acceptance testing, or SAT
  • Commissioning after transportation and installation
  • Scheduled maintenance
  • Troubleshooting after an abnormal event or repair

The factory result is especially valuable because it provides a baseline for later comparisons.

What Can a Winding Resistance Test Detect?

Winding resistance testing helps assess the condition of the transformer’s current-carrying path. Depending on the measurement pattern, abnormal results may indicate:

Possible issueWhat engineers may observe
Loose terminal or internal connectionHigher resistance in the affected measurement path
Poor tap-changer contactAn unexpected result at one or more tap positions
Damaged conductor or broken strandsA change compared with equivalent phases or previous results
Incorrect test connectionAn inconsistent result that changes after the setup is checked
Temperature differenceA broadly higher or lower reading compared with an uncorrected reference
Open circuitNo stable resistance reading through the intended path

A test result can indicate a possible problem, but it does not identify the exact fault by itself. Engineers should review the test setup and supporting evidence before reaching a conclusion. The U.S. Bureau of Reclamation identifies winding resistance measurement as a useful test for finding broken strands, loose connections and poor tap-changer contacts. usbr.gov

Why Does Temperature Matter?

Copper and aluminium winding resistance increases as the conductor temperature rises. This means a transformer can produce different resistance readings at the factory and on site even when its electrical condition has not changed.

For a meaningful comparison:

  1. Record the winding temperature, or the agreed method used to estimate it.
  2. Confirm the winding conductor material.
  3. Correct both readings to the same reference temperature.
  4. Compare the same winding, terminals, and tap position.

Ambient temperature alone may not represent the actual winding temperature, especially if the transformer has recently been operating. The reliability of the correction depends on how well the recorded temperature represents the winding.

Transformer Winding Resistance Temperature Correction

A commonly used correction formula is:

R₂ = R₁ × (T₂ + K) ÷ (T₁ + K)

Où :

  • R₁ = measured resistance
  • R₂ = resistance corrected to the reference temperature
  • T₁ = winding temperature at the time of measurement, in °C
  • T₂ = reference temperature, in °C
  • K = temperature constant; commonly approximately 235 for copper et 225 for aluminium, subject to the conductor material and applicable test method

Use the constants and reference temperature specified by the manufacturer, applicable standard, or project test procedure.

Example: Correcting a Copper Winding Reading

Suppose a copper winding measures 0.1200 Ω at 25°C. To compare it at a reference temperature of 75°C:

R₂ = 0.1200 × (75 + 235) ÷ (25 + 235)

R₂ ≈ 0.1431 Ω

The corrected value is approximately 0.1431 Ω at 75°C.

This is an illustrative calculation. It does not establish an acceptable value for a particular transformer.

How Should Engineers Compare Winding Resistance Results?

A resistance reading should be reviewed against the transformer’s design and available records. The most useful comparisons are:

1. Compare Equivalent Phase Measurements

For a three-phase transformer, compare equivalent measurement paths where the winding arrangement allows a meaningful comparison.

Record the actual terminals tested—for example, H1–H2 or X1–X0—rather than simply writing “Phase A.”

Important: Transformer winding connections and measurement paths can affect the expected values. Do not assume every terminal-to-terminal result must be identical without checking the vector group, winding arrangement, and manufacturer’s instructions.

2. Compare with the Factory Baseline

A site reading should be compared with the factory result for the:

  • Same winding and terminal pair
  • Same tap position
  • Same resistance unit
  • Same reference temperature
  • Comparable measurement method

A difference after transportation does not automatically mean the transformer was damaged. First verify the test conditions and measurement connections.

3. Compare Results Over Time

For an operating transformer, historical measurements can help engineers identify a developing trend.

For example, a gradual rise in corrected resistance on one measurement path may justify checking connections or tap-changer contacts. The investigation should consider other test results and the transformer’s operating history.

What Do Abnormal Results Mean?

The table below is a practical starting point for reviewing an unusual reading.

ObservationPossible explanationsRecommended next step
One comparable reading is higher than expectedPoor test lead contact, loose connection, damaged conductor, or contact issueVerify the setup, repeat the test and compare with the baseline
All readings are higher than the factory valuesDifferent winding temperature, incorrect temperature correction or measurement setupConfirm temperatures, conductor material and reference temperature
One tap differs unexpectedly from adjacent tapsTap contact or connection issue; test setup errorRepeat the measurement and review the tap-by-tap pattern
Reading does not stabilizeWinding inductance, insufficient stabilization time, poor connection or instrument settingsFollow the instrument and manufacturer’s procedure
Reading changes significantly after transportDifferent conditions, test connections or possible transport-related issueRepeat under comparable conditions and consult the manufacturer
No reading through the intended pathOpen circuit or incorrect connectionStop and investigate under the approved safety procedure

Practical rule: repeat and verify an abnormal measurement before treating it as a confirmed transformer defect.

What Are the Acceptance Criteria for Transformer Winding Resistance?

There is no single resistance value or percentage that can be applied safely to every transformer.

Acceptance depends on factors such as:

  • Transformer design and winding configuration
  • Terminal measurement path
  • Tap position
  • Measurement uncertainty
  • Winding temperature and correction method
  • Applicable standard and project specification
  • Factory baseline and historical results

Some projects specify a permitted phase-to-phase or baseline deviation. Buyers should confirm the applicable criteria before testing rather than assuming that a percentage found online applies to their transformer.

If a result falls outside the agreed criteria, the test report should document the deviation, repeat measurements, investigation, and agreed disposition.

Why Should Tap Positions Be Included in the Test?

Tap changers adjust the effective number of winding turns to change the voltage ratio. Their contacts and connections are part of the electrical path, so an issue may appear only at a particular position.

For example, a resistance pattern that changes as expected across several taps but shows an unusual value at one position may require further investigation.

Before FAT, ask the manufacturer:

  • Which winding has the tap changer?
  • Which tap positions will be measured?
  • Will individual readings be included in the report?
  • How will an abnormal tap-position reading be investigated?
  • Is the tap changer on-load or de-energized?

Testing must follow the equipment manufacturer’s instructions and the approved procedure. Tap operation during DC injection should only be performed with equipment and a procedure specifically designed for that purpose.

How Is a Transformer Winding Resistance Test Performed?

The exact procedure depends on the transformer and test instrument. A typical workflow includes:

  1. Review the transformer drawings, nameplate, terminal markings, tap arrangement, and test procedure.
  2. Isolate and prepare the transformer according to the approved electrical safety procedure.
  3. Record the winding temperature or agreed temperature estimate.
  4. Connect the test instrument to the specified terminals.
  5. Apply the appropriate DC test current and allow the reading to stabilize.
  6. Record the resistance, terminal pair, temperature, and tap position.
  7. Complete the required measurements and safely discharge the winding before removing connections.
  8. Correct and compare the results as required by the project specification.

Safety: Transformer windings store energy during DC testing. Testing and discharge must be carried out by qualified personnel using the manufacturer’s instructions and the approved site procedure.

Example: Comparing Factory and Site Test Results

The following is an illustrative scenario, not an actual DHDL project.

An EPC contractor receives an oil-immersed transformer for an industrial project in Vietnam. During site acceptance testing, one winding resistance reading appears higher than the factory value.

ItemFactory testSite test
Transformer conditionBefore shipmentAfter installation
Measured windingSame terminal pairSame terminal pair
Tap positionPosition 3Position 3
Recorded winding temperature25°C45°C
Initial observationBaseline establishedUncorrected value appears higher

The engineering team first checks the temperature correction, test leads, terminal identification, and tap position. After correcting both results to the same reference temperature, the difference becomes smaller.

If a difference remains outside the agreed project criteria, the team repeats the measurement and asks the manufacturer to review the full test data.

The lesson: an apparent change between FAT and SAT should trigger a structured comparison—not an immediate conclusion that the transformer is defective.

For a broader comparison of factory and site testing, see our guide to Transformer FAT vs SAT: Testing Checklist, Required Documents & Buyer Responsibilities.

What Should Buyers Request in a Winding Resistance Test Report?

A test report should make it possible to reproduce and compare the results later.

Report itemWhy it matters
Manufacturer, model and serial numberIdentifies the exact transformer
Rated capacity and voltageConfirms the equipment tested
Winding connection and terminal identificationDefines the measurement path
Tap positionAllows comparison of equivalent settings
Measured resistance and unitProvides the original test data
Winding temperature or estimation methodSupports temperature correction
Reference temperature and corrected values, if requiredEnables comparison with future results
Conductor material or applicable correction constantSupports the correct calculation
Test instrument identification and calibration informationSupports traceability
Test date and test personnelDocuments when and by whom testing was performed
Applicable procedure and acceptance criteriaShows how the results were assessed
Deviations and repeat-test resultsDocuments how abnormal results were resolved

For international projects—including those in Thaïlande, Nigeria, Uzbekistan, and Vietnam—agreeing on these requirements before manufacturing can reduce questions during inspection, shipping, and commissioning.

Transformer RFQ and Testing Checklist

When requesting a transformer quotation, provide the technical specifications and testing requirements together.

Basic Transformer Information

  • Rated capacity: kVA or MVA
  • Primary and secondary voltage
  • Frequency: 50 Hz or 60 Hz
  • Transformer type: oil-immersed or dry-type
  • Number of phases and vector group
  • Cooling method
  • Installation location and environmental conditions
  • Applicable standard and project specification

Testing and Documentation Requirements

  • Required routine and additional tests
  • FAT witness requirements, if any
  • Required tap-position measurements
  • Agreed acceptance criteria
  • Reference temperature and correction requirements
  • Required test report format and language
  • Third-party inspection requirements
  • SAT and commissioning documentation needs

For a more complete procurement list, read our Transformer RFQ Checklist.

Frequently Asked Questions

What does a transformer winding resistance test measure?

It measures the DC resistance of the selected winding and the connections included in the test path. Results help engineers assess winding connections and tap-changer contacts.

Is winding resistance the same as insulation resistance?

No. Winding resistance evaluates the resistance of the current-carrying path. Insulation resistance testing evaluates the electrical isolation between windings and ground, or between windings, according to the test setup.

Does a high winding resistance reading always mean a fault?

No. Temperature, test lead connections, tap position, measurement method, and instrument settings can affect the result. An abnormal reading should be verified and investigated against the relevant baseline and project criteria.

Why are factory winding resistance results important?

Factory results provide a documented baseline. Engineers can compare them with commissioning and maintenance readings when the same winding, terminals, tap position, and temperature conditions are considered.

Should every tap position be tested?

The required positions depend on the transformer design, applicable standard, manufacturer’s procedure, and project specification. Buyers should confirm the test scope before FAT.

Can winding resistance testing identify a shorted turn?

A winding resistance test alone may not reliably identify every shorted-turn condition. Engineers may need additional tests, such as a transformer turns ratio test or other diagnostic measurements, depending on the suspected issue.

Discuss Your Transformer Testing Requirements with DHDL

A useful winding resistance report should give your engineering team more than a pass or fail result. It should provide traceable measurements that can support future commissioning and maintenance decisions.

Dinghong Transformer supplies power and distribution transformers for industrial, utility, infrastructure, and renewable-energy applications.

If you are preparing a transformer RFQ, send us your capacity, voltage, frequency, installation conditions, applicable standard, and required test documents.

Email: service@dinghongtransformer.com

Explore a product: 66 kV High-Voltage Oil-Immersed Power Transformer